Request a Quote

IN-HEAD FIELDBUS OR PROFIBUS TRANSMITTER (TCX-5350B)

  • PROFIBUS PA ver. 3.0
  • FOUNDATION Fieldbus ver. ITK 4.6
  • Automatic switch between protocols
  • FISCO-certified
  • Basic or LAS capability with F.F.

Environmental Conditions
Operating Temperature -40°C to +85°C
Calibration Temperature 20°C to 28°C
Relative humidity < 98% RH (non-condensing)
Protection degree (enclosure/terminal) IP68 / IP00
Mechanical Specifications
Dimensions Ø 44 x 20.2 mm
Weight approx. 55 g
Screw terminal torque 0.4 Nm
Vibration DIN class B, IEC 60068-2-6 and IEC 60068-2-64
  2…25 Hz ±1.6 mm
  25…100 Hz ±4 g
Common Specifications
Supply voltage 9.0…30 VDC
Supply voltage in FISCO installations 9.0…17.5 VDC
Isolation voltage, test / working 1.5 kVAC for 60 s
Isolation voltage, Working voltage 50 VRMS / 75 VDC
Response time (programmable) 1…60 s
Quiescent current < 11 mA
Max current increase in the event of an error < 7 mA
Warm-up time 30 s
Signal / noise ratio Min. 60 dB
Updating time < 400 ms
Execution time, analog input < 50 ms
Accuracy Better than 0.05% of selected range
Signal dynamics, input 24 bit
EMC immunity influence < ±0.1% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span
Input Specifications
RTD type Pt25… 1000; Ni25… 1000, Cu10… 1000, lin. R, potentiometer
  Cable resistance per wire 50 Ω max.
  Sensor current Nom. 0.2 mA
  Effect of sensor cable
resistance
(3-/4-wire)
< 0.002 Ω / Ω
  Sensor error detection Yes
  Short circuit detection < 15 Ω
TC input types B, E, J, K, L, N, R, S, T, U, W3, W5
  Cold junction
compensation
< ±0.5°C
  Sensor error detection Yes
  Sensor error current:
When detecting / else
Nom. 4 μA / 0 μA
  Short circuit detection < 3 mV
  Voltage input
measurement range
-800…+800 mV
  Input resistance 10 MΩ
Output Specifications
PROFIBUS PA protocol Profile A&B, ver. 3.0
  protocol standard EN 50170 vol. 2
  address (at delivery) 126
  function blocks 2 analog
FOUNDATION Fieldbus protocol FF protocol
  standard FF design specifications
  version ITK 4.6
  capability Basic or LAS
  function blocks 2 analog and 1 PID
Observed Authority Requirements
EMC 2014/30/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
Approvals
ATEX 2014/34/EU KEMA 02ATEX1318 X
IECEx BVS 12.0035X
FM 3015609
CSA 1418937
INMETRO DEKRA 18.0006 X
NEPSI GYJ14.1101X
EAC Ex TR-CU 012/2011 RU C-DK.GB08.V.00410